High Voltage Cable

High Voltage / 2XS(FL)2Y, A2XS(FL)2Y 123kV Power Cable

High Voltage / 2XS(FL)2Y, A2XS(FL)2Y 123kV Power Cable Zoom

Application

The HV power cables contained within this datasheet are suitable for the primary distribution of power up to a maximum network voltage of 110kV. The cables are triple extruded to the latest IEC standards using proprietary materials on modern catenary line equipment. The foil laminate layer provides an effective moisture barrier and imparts a limited increase in mechanical protection although it should be noted that these cables should be adequately protected from potential mechanical damage. Waterblocking tape options ensure that, should the cable be damaged, repair lengths and associated works are kept to a minimum. The cables are provided with a High Density Polyethylene sheath selected to offer the best compromise between abrasion resistance and flexibility. The range can be customised to meet specific project requirements, etc.

Cable Standards

IEC 60840, HRN HD 632

Construction

Conductor
Class 2 copper or aluminium conductor, compacted or segment according to BS EN 60228 (previously BS 6360)
 
Conductor Screen
Extruded semi-conductive XLPE (Cross-Linked Polyethylene)
 
Insulation
XLPE (Cross-Linked Polyethylene)
 
Insulation Screen
Extruded semi-conductive XLPE (Cross-Linked Polyethylene)
 
Separator
Water swellable semi-conductive tape
 
Screen
Copper wire screen, with a counter helix of copper tape
 
Separator
Water swellable semi-conductive tape
 
Moisture Barrier
Aluminium or Copper tape with copolymer
 
Sheath
HDPE (High Density Polyethylene)
(To be specified at time of order. Other options available)

Characteristics

Voltage Rating (Uo/U)
64/110kV
 
Highest Network Voltage (Um)
123kV
 
Maximum Conductor Temperature
+90°C
 
Short Circuit Temperature
+250°C
 
Operating Temperature
-30°C to +90°C
 
Minimum Installation Temperature
-20°C
 
Sheath Colour
Black

Full technical specification available here: View | Save

Fast Quote

Colour :

Length (m) :

Add To fastquote
Eland Part No.Conductor TypeNo. of CoresNominal Cross Sectional Area <br />(mm^2)Electrical Protection <br />(mm^2)Nominal Overall Diameter <br />(mm) Nominal Weight <br />(kg/km)
A9K2XSFL150Copper11509564.95035
A9K2XSFL185Copper11859564.55272
A9K2XSFL240Copper12409564.85742
A9K2XSFL300Copper13009565.16210
A9K2XSFL400Copper14009567.47208
A9K2XSFL500Copper15009571.78322
A9K2XSFL630Copper16309575.29886
A9K2XSFL800Copper18009582.612042
A9KA2XSFL150Aluminium11509564.94128
A9KA2XSFL185Aluminium11859564.54153
A9KA2XSFL240Aluminium12409564.84283
A9KA2XSFL300Aluminium13009565.14397
A9KA2XSFL400Aluminium14009567.44880
A9KA2XSFL500Aluminium15009571.75433
A9KA2XSFL630Aluminium16309575.26064
A9KA2XSFL800Aluminium18009582.67100
A9KA2XSFL1000Aluminium110009584.77795
A9KA2XSFL1200*Aluminium112009595.78350