What is System Redundancy in Power Networks?

Designing resilience into the infrastructure from the outset is essential in the event of failure. Downtime is costly for many industries. Power systems, cooling equipment, and the cables that connect them all contribute to overall availability, and the way these elements are configured determines how well a facility can withstand faults, maintenance requirements, or unexpected load demands. For critical systems they must be designed to maintain service continuity even when individual components or entire subsystems are taken out of operation.

Power system redundancy models explained

Understanding the concept of N

N represents the capacity required for a system to operate at full load under normal conditions. If a facility - let's take a data centre as an example - requires four uninterruptible power supply (UPS) modules to support its critical power demand, N is four. If maintaining environmental conditions requires two cooling units, N is two. Everything beyond this point is additional capacity introduced to protect against failure or downtime.

Keeping with the data centre example, a Tier I site provides basic non-redundant infrastructure suitable for environments where occasional downtime is acceptable.

How N+1 offers protection against single failures

N+1 describes a system with the required operational capacity plus one additional component that can take over if something fails or needs to be removed for maintenance. It is one of the most common approaches used because it balances resilience with efficient use of space and resources.

A typical example might involve installing a fifth UPS where only four are needed, or adding an additional cooling unit to ensure temperature control is maintained even if one is offline. The same logic applies to electrical distribution equipment and cable runs. Providing a spare route or spare unit prevents a single failure from affecting service availability. Many concurrently maintainable designs are built around this principle.

In a data centre, that would equate at a lower level to Tier II: redundant components introduced, aligned with N+1 principles. At the higher end of the scale is Tier III, incorporating concurrent maintainability and multiple power and cooling paths with diverse routing.

How 2N provides complete system duplication

While N+1 provides a safety margin, 2N creates an entirely independent second system that mirrors the first. Each system is capable of supporting the full load on its own. This approach removes the need to share infrastructure between power paths and offers protection not just against individual equipment failures but also against wider faults that could affect an entire power train.

In a 2N layout, the A and B power feeds are kept entirely separate, including incoming supply, UPS systems, switchboards, power distribution units (PDUs), and the cable routes that deliver power into the racks. Physical separation is a critical element of the design. Independent containment reduces the risk that a single event, such as mechanical damage or fire in a riser, affects both paths simultaneously. Whilst clearly adding significant additional costs to any build-out and requiring double the space allocation, organisations with the highest uptime expectations, such as financial trading environments, often adopt this configuration.

As the final data centre example, this would equate to Tier IV: the highest level of resilience with 2N or equivalent fault tolerant designs that allow a facility to remain fully operational even if an entire system fails unexpectedly.

Beyond the standard redundancy models

Some operators extend redundancy further with configurations such as 2N+1 or modular systems designed to provide additional standby capacity. These architectures allow maintenance or component removal even during peak operational periods. Though not required for most cases, they reflect the increasing emphasis large-scale operators place on ensuring service continuity across all scenarios.

 

Icon - Cable

Cable Portfolio

View our comprehensive range of power, data, control and instrumentation cables and accessories

Go
Icon - Lab Black

Cable Testing

Read more on the different tests we conduct in our Cable Laboratory

the Tests
Case Studies Icon

Case Studies

Read about some of the projects we've worked on, spanning all industries

Read on