Crimp & Lug Testing for Power Cable Accessories

BS EN 61238-1 is the standard that covers compression and mechanical connnectors for power cables at rated voltages of up to 36kV. There are two classes defined within the standard - Class A which includes short circuit testing and Class B which does not include this testing.

Crimp testing and lug testing sees three samples subjected to tensile testing, The samples must be 40x the cross-sectional area in mm2 for aluminium conductors, and 60x the cross-sectional area in mm2 for copper conductors (in N) up to a maximum of 20,000N.

A further six samples are the subjected to tests in the following sequence:

Class A
Initial resistance measurements
Heat cycling to raise the reference conductor to 120oC
Resistance measurements after 200 cycles, before short circuit
Short circuit at 25kA raising the conductor to between 250oC to 270oC
Resistance measurements after 200 cycles after short circuit
Resistance measurements every 75 cycles up to a total of 1000 cycles
Class B
Initial resistance measurements
Heat cycling to raise the reference conductor to 120oC
Resistance measurements after 250 cycles
Resistance measurements every 75 cycles up to a total of 1000 cycles

 

For both Class A and Class B tests on crimps and lugs, the variations in resistance are analysed statistically

Icon - Cable Calculator

Cable Sizing Calculator

Supporting Low Voltage cable sizing to BS and IEC standards with our easy-to-use calculator

Try it now
Cable (1)

Custom Cable Design

Tailoring cables to meet bespoke requirements of performance or environmental challenges when off-the-shelf options are unavailable.

Read more
Icon - CPD training

CPD Cable Training

Expert cable tuition from our experts with CPD-certified cable training and tailored cable learning programmes

Courses